Products » Gensets » 50Hz » Upto 15 KVA
|
| ENGINE |
Parameters |
Unit |
5kVA |
7.5 / 10 5 kVA |
12.5kVA |
15kVA |
| Engine Model |
15LD440 |
2185 GM |
2185 GM |
3255 GM |
| Gross Power - (110%) |
bhp |
9 |
18 |
18 |
25 |
| Speed |
rpm |
3000 |
1500 |
1500 |
1500 |
| Cooling system |
Air cooled |
Water Cooled with Radiator
|
| Aspiration |
Natural |
Natural |
Natural |
Natural |
| No. of cylinders |
1 |
2 |
2 |
3 |
| Displacement |
cc |
442 |
1365 |
1365 |
1895 |
| Governing Class |
A2 |
A1 |
A1 |
A1 |
| Starting System |
12V DC |
| ALTERNATOR |
Type |
Brushless, Single / Three Phase, Class H Insulation |
| Voltage |
volts |
230 |
415 / 230 |
415 |
415 / 230 |
| Speed / Frequency |
rpm/hertz |
3000 / 50 |
1500 / 50 |
1500 / 50 |
1500 / 50 |
| CONTROL PANEL |
AMF / Manual control panel - as per specific requirement / application |
| FUEL TANK |
Capacity |
litres |
50 |
250 |
250 |
250 |
| BATTERY |
Capacity |
Ah |
35 |
As per standard fitment |
| ACOUSTIC ENCLOSURE |
Length |
mm |
1400 |
2150 |
2150 |
2300 |
| Width |
mm |
900 |
1030 |
1030 |
1030 |
| Height |
mm |
1350 |
1250 |
1250 |
1350 |
| DG SET |
Weight |
kgs. |
390 |
800 |
800 |
850 |
|
Note: |
Above specifications are subject to change without notice due to continuous technical developments.
All the above engine models conform to IS 10000 specifications. Engine governing as per BS 5514.
Alternator Reputed make conforming to respective IS standards. |
|
|
|
|
|